Careers Trade Shows Rep Locator Tech Support
Product Index Software Demos Contracting Us Site Registration

 

General

Features, Benefits & Applications

Principle of Measurement

Test Connection for Power Transformer

Test Procedure

Scope of Supply

Tech Specifications

Downloadable
Spec Sheet

Order LIterature & Inquire for More Info

RVM 5462

System

Gain (Attenuation)

0 dB to 75 dB in 5 dB steps

Attenuator accuracy

1%

Gain

3000

Input Impedance

50 Q

System Noise

< 12 pv referred to input on highest gain range

Filters

High Pass - 20, 50, 80 kHz

 

Low Pass - 100, 200, 400 kHz

 

500 kHz

Test Voltage

Measuring Range

50...2000V DC; adjustable in 1V steps

Basic Setting

2000 V DC

Max. Deviation from
the Set Value

± 0.2 %

Current–Carrying Capacity (permanent)

5 mA

Max. Short Circuit Current

200 mA, 100 ms

Delayed Short–Circuit Protector

Charging and Discharging Time Range

tc, td 10 ms...99 999 s

Charging/Discharging
Time Relation (tc/td)

0.1...10, Basic setting 2

Charging and Discharging Current Measurement Capability

20 mA...10 pA (max resolution: 1 pA)
Error limits ±1% + 5 pA

Resistance Measuring Range

1 M...1000 G
Error limits (100 G) ± 1.5%
Electrometer Data

Measuring Range

-200...+1000 V

Error Limits

± 1%

Current Input

<= 1 pA

Operating Conditions

Voltage Supply

85...260VAC, 50/60 Hz

Power Input

max. 40 VA

Temperature Range

Instrument operating temperature 0°C...40°C; Recommended test object temperature >= 8°C

Mechanical

Dimensions

47 x 19 x 37 cm (18.5" x 7.5" x 14.6")

Weight

10 kg (22 lbs)

Applicable Standards

 Reference and rated operating conditions as per IEC 359, rated range of use I. This instrument is designed in accordance with the safety requirements of VDE 0411/part 1 and IEC 348 (safety class I).